The thyristor-type static excitation system, due to its many advantages, excellent response characteristics,easy maintenance and simplified main machine construction, is now extensively used for medium-and large-capacity hydro-or steam-turbine generators.

The voltage regulator and potential source static excitation system functions to control the voltage of an synchronous  generator by directly controlling the generator's DC field current. The static excitation system is composed of the followings:
Thyristor rectifier bridge and thyristor elements:
The 3phase full bridge rectifier circuit has fast response characteristics. A compact cubicle design is realized with the large on-state current and high reversed voltage flapack type thyristor elements, and forced air cooling. The thyristor elements are installed in a tray, and can be exchange during operation. For better cost performance, a tray-less-type can also be manufactured.
Field Flashing
The field flashing circuit is necessary when a generator is started, because of self excitation system. A DC battery is usually used as the initial excitation power supply. An AC power supply can also be adopted by means of rectifiers and a transformer.
Field suppression
The de-excitation function is to reduce rapidly field energy when needed and also to separate the rotor circuit from the excitation system. The DC field circuit breaker is generally used. For better cost performance, a static field circuit breaker system can be supplied. This system reduce the field energy by reversing the excitation voltage by rectifier gate controls.
Over voltage protections
The C-R absorbers and varisters are installed in each AC and DC circuit for over voltage protections of thyristor elements. In large capacitance system, a crowbar circuit is adapted on DC circuit.
Excitation transformer
The excitation transformer reduces the supply voltage to the level required for excitation. A dry-type for small capacity or a oil-type for large capacity is generally used.
Monitoring devices
The alarms for thyristor fuse blown, cooling fan failure and air temperature high are available. A rotor temperature converter and field earth detector can be installed in excitation cubicles optionally.
etc..
source: excitations system

Excitation systems have a powerful impact on generator dynamic performance and availability, it ensures quality of generator voltage and reactive power, i.e. quality of delivered energy to consumers. Following types are common:
  • Brushless excitation systems, with rotating exciter machines and Automatic Voltage Regulator (AVR), or
  • Static excitation systems (SES), feeding rotor directly from thyristor bridges via brushes.
Main functions of excitation system are to provide variable DC current with short time overload capability, controlling terminal voltage with suitable accuracy, ensure stable operation with network and/ or other machines, contribution to transient stability subsequent to a fault, communicate with the power plant control system and to keep machine within permissible operating range.                      


Thursday, July 21, 2011

Controlled discharging of Inductive HV Equipment

 HV equipment need to be discharged prior to any maintenance work.  The discharge is usually done with an earthing rod after verifying that there is no voltage present on them with an non-contact voltage detector.

In the case of inductive equipment such as transformers and motors with high inductance value in their windings, a controlled discharge needs to be carried out.  Inductive components such as windings in transformers and motors have high inductance.  Sudden discharge of these windings will create a high discharge current and a rapid change in the flux which will result in a high voltage pulse (according to Lenz' Law). This can damage the winding insulation.

The controlled discharge is carried out with a discharge rod with a resistor in series.  The resistor used is a special non linear resistor which has a reverse temperature coefficient which means that as the temperature increases the resistance falls.  When the discharge is started, the resistance is high. As current flows through the resistor, the temperature of the resistor rises and its resistance falls.  Thus the current flow is increased.

The resistor ensures that the discharge is gradual.

Arcing ground

Arcing Grounds is a phenomenon which is observed in ungrounded three phase systems.  In ungrounded three phase systems operating in a healthy balanced conditions, capacitances are formed between the conductors and ground.  The voltage across these capacitances is the phase voltage. 


Now, in the event of a ground fault, the voltage across the faulty conductor becomes zero while the voltages across the healthy conductors increase by a factor of 1.732. 

The arc caused between the faulty conductor and the ground gets extinguished and restarts many times, this repeated initiation and extinction of the arc across the fault produces severe voltage oscillations of the order of nearly three to four times the nominal voltage. 

This repeated arcing across the fault due to the capacitances between the conductors and the ground is known as arcing grounds.  Arcing grounds can be eliminated by the use of Peterson Coils and Arc Suppression Coils

Duty cycle:: for motor

The relationship between operating and rest period of a motor is known as duty cycle. It is important while choosing a rating of a motor for our particular application. The international Electrotechnical commission has defined the following standard:


S1 Continuous duty The motor works at a constant load for enough time to reach temperature equilibrium.
S2 Short-time duty The motor works at a constant load, but not long enough to reach temperature equilibrium. The rest periods are long enough for the motor to reach ambient temperature.
S3 Intermittent periodic duty Sequential, identical run and rest cycles with constant load. Temperature equilibrium is never reached. Starting current has little effect on temperature rise.
S4 Intermittent periodic duty with starting Sequential, identical start, run and rest cycles with constant load. Temperature equilibrium is not reached, but starting current affects temperature rise.
S5 Intermittent periodic duty with electric braking Sequential, identical cycles of starting, running at constant load and running with no load. No rest periods.
S6 Continuous operation with intermittent load Sequential, identical cycles of running with constant load and running with no load. No rest periods.
S7 Continuous operation with electric braking Sequential identical cycles of starting, running at constant load and electric braking. No rest periods.
S8 Continuous operation with periodic changes in load and speed Sequential, identical duty cycles run at constant load and given speed, then run at other constant loads and speeds. No rest periods.

Electrical news

To know about latest findings and news visit Electrical news..

Super Capacitors

Capacitors having very high capacitance reaching up to 500 farads is called super capacitor. They are also called ultra or double layer capacitor. The main principle behind the super capacitor is similar as normal capacitor but are manufactured with nano-technology which enables the dielectric to have a large surface area hence greater quantity of charge is stored. The commonly used dielectric is electrolytic soaked separator and the electrode is activated charcoal.  
              These stores energy just like batteries but advantageous due to lighter in weight, environmentally friendly, can be charged and discharged repeatedly unlike the battery, life is about 1000 times that of the battery. Their uses are in camera, electric automobiles, power conditioner, welders etc. Super capacitors can supply short burst of power and are useful when heavy loads are applied suddenly.  They also charge faster and absorb voltage transients better while the battery supplies the regular power requirement. They are also used in automobiles to where they can be charged easily and are particularly effective in recovering energy from the transmission systems through regenerative braking. The downside of supercapacitors is the low energy to weight ratio as compared to batteries.  Further advances in technology may narrow out this difference.

Tuesday, July 19, 2011

Difference between salient pole and non-salient pole rotor used in synchronous generator.

synchronous machine can be characterized by the type of rotor used. Rotors used in Synchronous alternators can be classified into:
1)Salient and
2)Non-Salient Pole Rotors or cylindrical rotors
Salient pole rotors are used in application with speeds from 100 to 1500rpm. They are alternative known as "projected pole" type of rotors. The poles mounted on the rotor are made of lamination's made of steel. The poles are connected to the rotor shaft by means of dovetail joints. Each pole has a pole shoe around which the winding is wound. The salient pole rotor is generally used in applications where the prime mover is a hydel turbine or a combustion engine which have low or medium speeds. Salient pole rotors usually contain damper windings to prevent rotor oscillations during operation. Due to low speed, they are constructed with higher no. of pole (ranging from 8-24 or higher) to achieve system frequency so they can be said as higher pole machine. Almost all hydro power uses salient pole rotor synchronous generator.
                               Non-salient pole rotors are generally used in application which operate at higher speeds, 1500rpm and above. The prime movers in these applications are generally gas or steam turbines. These are sometimes known as "drum rotors". The rotor is a cylinder made of solid forged steel. The slots on which the windings are fixed are milled on the rotor. The number of poles is usually 2 or 4 in number. Since these rotors are cylindrical, the windage loss is reduced. The noise produced is also less. These rotors have higher axial length. These rotors do not need damper windings. Due to high speed, they are used with gas turbine and high speed steam turbine in nuclear power plant and thermal power plant.